Lightolier güç kaynağı L1PH Series Kılavuz

PDF Kılavuzları
2 Sayfalar İngilizce

Lightolier güç kaynağı L1PH Series
Sayfalar
İN
2
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
Unit 14.0 kVA
Battery 2,995 lbs.
Cabinet (1,358 kg)
Electronics 465 lbs.
Cabinet (211 kg)
Total System 3,460 lbs.
(1,569 kg)
L1PH Series Uninterruptible Power Supplies
L1PH
Page 1 of 2 14.0 kVA Single Phase UPS System
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier
a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Overall Characteristics
86% throughput efficiency
Operating temperature range 32°F (0°C) to 104°F (40°C)
Internal maintenance by-pass is standard
Main load disconnect switch standard
Double conversion, no interruption
Standard backup time of 90 minutes, other run times optional
Output circuit breakers and normally-off loads optional
Housing
Free standing, NEMA 1 enclosure
Acid resistant powder coat finish
Multiple conduit entries
Metering/Controls
Standard
Alpha-numeric front panel display with 14 metered measurements and
53 messages/alarms
Normal, caution and alarm indicating LEDs
Audible failure alarms with silence switch
Dry contact for remote failure alarm
“D” type 9-pin computer interface connector (see pin config. on back)
Programmable battery monitor with alarm
Optional
Diagnostics software for remote computer (PC) monitoring and control
Stand-alone remote display mimics all measurements, indications and
alarms shown on the front panel display
Additional RS-232 input/output port for remote monitoring and system
control
Electrical
Sine Wave Output
Completely solid-state Pulse Width Modulation (PWM) inverter
16-bit microprocessor control
Input power factor correction maintains power factor at 0.99
Transient response 5%; Recovery time, 10 mS (100% load step)
3:1 crest factor capability
Inverter output distortion 2.5% THD (at unity power factor)
Output voltage regulation ±6% of nominal at full load
Frequency within ±0.05% of nominal
Inverter efficiency 84%
Load power factor capability is 0.5 leading to 0.5 lagging
(Continued on page 2)
NOTE: Input circuit
breaker not available.
Input switch is
standard.
L1PH I 14.0 S
SERIES INPUT SYSTEM BASE BATTERY OUTPUT OUTPUT # ON 2ND NORMALLY # OF NOL
VOLTAGE TYPE SIZE TYPE VOLTAGE CKT BRKRS
1
VOLTAGE OFF LOAD NOL VOLTAGE
L1PH = Single
Phase
Uninterruptible
Power
Supplies
14.0 = 14.0 kVa
2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage
(Consult
Factory)
1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage
(Consult
Factory)
Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9
0
1
2
3
4
5
6
7
8
9
10
11
A = No
B = Yes
C = Yes w/ Time
Delay Timer
0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11
12 = 12
X = None
A = 1st
B = 2nd
I = ETL Listed
to UL 924 for
Emergency
Lighting
Applications
S = Sealed
Lead Calcium
34.0”
86.4 cm
33.0”
83.8 cm
70.0”
177.8 cm
Battery
Cabinet
33.0”
83.8 cm
30.0”
76.2 cm
43.5”
110.5 cm
Electronics
Cabinet
İlgili Kılavuzlar Lightolier güç kaynağı L1PH Series